Project Description

CASE STUDY

Natural smoke ventilation utilising a variety of certified solutions

Project

Newton House is a brand new Housing 21 Extra Care Living development in Penrith. It promotes independent living for people over the age of 55, with access to on-site care. The development offers 54 one and two bedroom apartments.

Newton House provides fully accessible facilities for residents and visitors. These include a restaurant, hair salon, residents’ lounge, activity room and communal gardens.

System

For the natural smoke ventilation system at Newton House, Dyer provided roof vents, dampers and louvres, and supplied and installed the controls in order to ventilate the communal areas.

Three staircases are ventilated by certified smoke vent rooflights, each fitted with a KA 54 chain drive.

Each of the three internal corridors are ventilated via smoke shafts with smoke dampers and grilles (with concealed drives) at each corridor level and a rooflight at the head of the shaft.

Dual colour aluminium double glazed louvres each fitted with a single LDF louvre drive, ventilate the six corridors.

All staircase roof vents and louvres are CE marked and tested to EN 12101-2. The shaft dampers are CE marked and tested to EN 12101-8.

Dyer supplied and installed a multizone smoke ventilation control panel with 72 hour battery back up, with one breakglass reset switch for each zone. The control panel will receive signals from the fire alarm to individually trigger each zone. When a corridor zone is triggered, the vent at the head of the adjacent staircase will open. If a smoke shaft inlet vent is triggered, all remaining vents will be locked in the closed position to prevent spread of heat and smoke between floors.

The end of corridor louvres can be used for natural day-to-day ventilation when required. Each has a switch located nearby, when pressed, will open the louvres to 25%, allowing fresh air to enter the corridors.

RELATED CASE STUDIES

LATEST TWEETS…

@dyerenvironment

- 3 days ago

We're doing our Fire Awareness & Extinguisher Training at the Dyer office today. It's important to keep on top of fire safety! https://t.co/2OMT1QN9aI
h J R
@dyerenvironment

- 8 days ago

The EN 12101-2 certified F100 NSHEV dome vent is ideal for staircase and corridor smoke extraction on flat and pitched roofs. See our site for performance features and technical data - https://t.co/E0x7JIU4Ef https://t.co/S17AJTaHX1
h J R
@dyerenvironment

- 14 days ago

@SmokeContAssoc: The Smoke Control Association (SCA) has released a new reference guide (Guidance on Smoke and Heat Exhaust Ventilators) designed to encourage best practice and raise industry standards. Find out more here https://t.co/1BzavzN7oC https://t.co/esaWMUlUw6
h J R
@dyerenvironment

- 29 days ago

Merry Christmas and Happy New Year from all of us at Dyer!🎄 Thank you for your cooperation throughout 2021. We will return Wednesday 5th January 2022. https://t.co/trSraKQPvF
h J R
@dyerenvironment

- 31 days ago

Dyer worked with @LamiluxUK and provided the controls for this natural smoke ventilation system. https://t.co/IvMEx0CVag
h J R